A/RH5-D | ACI | Humidity

Humidity Sensor, Duct, 7.25 Probe, ±5.00%, Field Selectable Output, No Temperature Sensor

Brand:ACI

MPN:A/RH5-D

SKU:A/RH5-D

List Price:

$258.00

Today's Price:

$134.16



product specifications

Accuracy

5%

Application

Humidification, Dehumidification, Supply, Discharge, Return Air, Economizers, Clean Rooms, Data Centers, Process Control, Schools, Hospitals, Office Buildings

Housing Material

Poly

Mount

Duct

Output

4 - 20 mA

Probe Length

7.25 in

Power Requirements

24 VAC/VDC

product series specifications

Accuracy: ±5% @ 77°F (25°C) from 10% to 95%

Stability: ±2% RH/5 years

Supply Voltage: 12-40 VDC or 18-28 VAC

Signal Output: 4-20 mA @ 300O, 0-5/10 VDC @ 4kO min, (field selectable) except SP 0-5/10 VDC only

Measurement Range: 0% to 100%

Sensing Technology: Capacitive

Operating Temperature:

Room: 32° to 122°F (0° to 50°C)

Duct/OSA: -40° to 140°F (-40° to 60°C)

Dimensions:

Room: 3.8"H x 2.8"W x 0.9"D (9.8 x 7 x 2.3 cm)

Duct: 3.6" (9 cm) Ø head with 8.15"L (20 cm) probe 0.75" (1.9 cm) Ø

OSA: 3.6" (9 cm) Ø head with 3.0"L (7.6 cm) probe 1.4" (3.6 cm) Ø

Enclosure:

Room: Plastic Delta-style

Duct/OSA: Plastic weatherproof

Weight:

Room: 0.22 lb (0.1 Kg)

Duct: 1.2 lb (0.54 Kg)

OSA: 0.6 lb (0.27 Kg)

SP: 0.2 lb (0.09 Kg)

Approvals: CE, RoHS

Warranty: 5 years

product series features

  • Popular room housing
  • Five-year warranty
  • Duct and OSA twist-off NEMA 4 housing
  • 24 VDC or 24 VAC power
  • Field selectable current or voltage outputs
  • Single point field calibration
  • Optional temperature sensor

more information & related documents

Series Description

The ACI A/RH5 Series relative humidity transmitters are specifically designed for HVAC/BAS applications and have proportional 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output for 5% measurement. It is available for room, duct, outside, and stainless steel wall plate applications. The A/RH5 Series has on board DIP switches which allow the user to select the desired output signal and can be powered by AC or DC power sources.

Kele Description

5% DUCT RH XMTR, NO TEMP

Manufacturer